DIERS Benchmarks

Case 3  Two-phase hybrid Flow             Download

DIERS two-phase hybrid flow benchmark is based on the same relief pressure of 72.5 psia but 5 psi is nitrogen and 67.5 psi is the steam.  The physical properties of the liquid remain the same but now the physical properties of the nitrogen/steam mixture is based on mixture properties based on partial pressures of each gas.

Case 5 Two-phase high viscosity hybrid flow          Download

DIERS two-phase high viscosity hybrid flow is the save as above except the liquid viscosity is based on the equation µ = exp(A + B/ T(oK)), where B = 2959.3 and A = -1.74.  The viscosity varies with temperature.

Mach II   Nozzle Results & Piping Results

                                         Flowrate (lbs/hr)              Choke (psia)              Quality (x)           Inlet dP / %Pset         Outlet dP / %Pset       Pipe

Hybrid Flow                   88,839                                  60.1                            0.025                      ---------                      ----------                 nozzle

                                           87,305                                  59.1                            0.026                     0.75 /1.4                    6.0 / 11.4               4 X 6

                                           88,364                                 59.8                             0.026                    0.23 / 0.44                 6.0 / 11.4                6 X 6

DIERS Results Hybrid Flow

   RRERSP                        98,947                                 60.9                             0.0207                       ------                              -------               nozzle

   RRERSP                        94,855                                 59.8                             0.0221                     0.7 / 1.3                      6.3 / 12.1           4 X 6

   RRERSP                        96,971                                 60.3                             0.0213                     0.1 / 0.2                      6.7 / 12.9           6 X 6

Two-phase high viscosity hybrid flow

                                          88,839                                 60.1                              0.025                        -------                            ------                    nozzle

                                          86,494                                 58.6                              0.027                    1.0 / 2.0                          6.0 / 11.4            4 X 6

                                          88,245                                 59.7                              0.026                    0.29 / 0.6                        6.0 / 11.4            6 X 6

                                         

DIERS Results high viscosity hybrid Flow

    RRERSP                     96,643                                  60.9                             0.0207                     --------                            -------              nozzle

    RRERSP                     91,834                                  59.5                             0.0223                   1.0 / 2.0                          6.6 / 12.6        4 X 6

    RRERSP                     93,139                                  60.2                             0.0214                    0.3 /0.5                          6.8 / 13.1        6 X 6